HVJ5 1.14kv 125A AC vacuum contactor is designed for long-distance making and breaking of circuit, frequent starting and controlling of AC motors in the power systems, with AC 50Hz-60Hz, rated voltage of 1,140V and rated current to 125A. It also can be equipped with thermal relay and all kinds of protection apparatus like electromagnetic starter, especially applied to explosion-proof starter and so on.

  1. Main technical parameter

Rated voltage: 1140 V

Control voltage: 36V, 110V, 220V, 380V

Rated current: 125A

Opening distance: 1.8±0.2 mm

Over travel: 1±0.2 mm

Final pressure: 30±3 N

Main circuit power frequency voltage withstand: 4200 V

Auxiliary circuit power frequency voltage withstand: 2500 V

Control circuit power frequency voltage withstand: 2000 V

Making capacity: 10Ie,100 times

Breaking capacity: 8Ie,25 times

Limit breaking current(A): 2000,3 times

Electricity life times AC3: 60*104

Electricity life times AC4: 60*104

Mechanical life times: 300*104

Overload capacity: 8Ie 10 S

 Remark: “Ie” is Rated current of main circuit.

 

Product model

Rated voltage (V)

Rated currentMain circuitA

Main contacts parameters

Power frequency voltage 
resistance V(effective value)

 

Main circuit

Control circuit

Opening distancemm

Over travel
(mm)

Final pressure
(N)

Main circuit

Auxiliary circuit

Control circuit

 

HVJ5-1.14/125

1140

36.110.220.380

125

1.8±0.2

1±0.2

30±3

4200

2500

2000

 

 

Product model

Making capacity

Breaking capacity

Limit breaking current(A)

Electricity life times

Mechanical life times

Overload capacity

AC3

AC4

HVJ5-1.14/125

10Ie,100times

8Ie,25 times

2000,3 times

60*104

6*104

300*104

8Ie 10S

 Remark: “Ie” is Rated current of main circuit.

 